Available Items.

  • 10/5A
  • 15/A
  • 20/5A
  • 30/5A
  • 40/5A
  • 50/5A
  • 60/5A
  • 100/5A
  • 150/5A
  • 200/5A
  • 250/5A
  • 300/5A
  • 400/5A
  • 500/5A
  • 600/5A
  • 800/5A
  • 1000/5A
  • 1200/5A
  • 1500/5A
  • 1600/5A
  • 2000/5A
  • 2500/5A
  • 3000/5A

General Specification:

  • Applicable Standard : IEC/ EN 60044-1 ,BS 3938 , IS 2705-1 , IEC 185
  • Rated Secondary Current : 5A standard ( 1A optional)
  • Rated Burden : See Product range (Customer specified burden on request)
  • Acc. Class : See product range (High accuracy 0.2s,0.1 upto 0.05 on request)
  • Test Voltage : 4 KVeff ,50 Hz 1 min
  • Thermal Short Circuit Current ( Ith): 60 X In
  • Dynamic Short Circuit Current (Idyn): 2.5 X Ith
  • Instrument Security Factor ( ISF) : ≤ 5 (Customer specified ISF value on request)
  • Rated Continuous Thermal Current ( CTC) : 1.2 In (higher CTC on request )
  • Insulation Class : E ( 120°C max )
  • System Voltage : 720 V max
  • Operating Frequency :50 – 60 Hz
  • Case : Non -flammable Plastic, UL 94V-0
  • Protection Class : IP20
  • Temp. Range : Working -20°C to +55°C, Storage -50°C to +80°C